Differential pressure measurement is trusted as a way for monitoring the amount of closed vessels. Oftentimes, operators use individual instruments with an output signal or on-site display. On the other hand, a more precise and fault-immune solution is the measuring arrangement developed by WIKA using two process transmitters in a primary-secondary relationship.
Each level monitoring application using differential pressure measurement is founded on the following principle: For the amount of the contents in the vessel, the differential pressure between your liquid and the gaseous phase is determined. In addition, the hydrostatic pressure, the precise density of the medium and the vessel geometry are contained in the calculation. Typical measuring instruments have two adjacent process connections for the pressures P1 and P2. For level measurement, a capillary must bridge the pronounced distance between the two measuring points.
Astounded with two process transmitters as Primary instrument (right) and Secondary instrument. This measuring arrangement for level monitoring may be used flexibly, e.g. for info on the mixing ratio of liquids.
Connection via signal cable
When monitoring the particular level using electronic differential pressure measurement, on the other hand, both measuring points have one process transmitter each. For instance, the WIKA models CPT-2x and IPT-2x are suitable for this. Both transmitters are arranged as Primary instrument and Secondary instrument. They’re connected, purely electrically, via a signal cable and so are therefore not vunerable to disturbances. THE PRINCIPAL instrument supplies the Secondary instrument with power. The Secondary instrument is parameterised via a serial interface or through the display on the principal instrument. Finally, communication occurs via an internal bus.
Level monitoring in a closed tank
Application example
The figure on the left shows an average application example for level monitoring with electronic differential pressure measurement on a liquid tank. The Secondary instrument measures the pressure P1, in this case the gas pressure, and transmits it to the Primary instrument. This detects the pressure P2, here the pressure in the liquid column in the bottom of the tank. The Primary instrument calculates the differential pressure from P1 and P2. Using Shrewd measured value and taking into account another parameters mentioned, it determines the volume in the tank as an indication of the particular level. This value could be output either being an analogue or digital signal to the control room and/or to the display of the Primary instrument.
Benefits of the measuring arrangement with two process transmitters
The method for level monitoring described here has several advantages in comparison with a conventional method, for example, with a differential pressure transmitter:
Higher accuracy and ?turndown?
Process transmitters deliver higher degrees of accuracy. Regarding the WIKA models, these are up to 0.05 % of the set span. In Insider , there is the chance of ?turndown?, the individual setting of a particular measuring span (that is also possible retrospectively with instruments that are already installed.)
Minimised temperature effect
Transmission via signal cable with electronic differential pressure measurement minimises the temperature effect. On the other hand, the capillaries used in the traditional measuring method are a lot more susceptible here. This, in turn, can ultimately affect the measuring result.
Fast commissioning
The electronic measuring arrangement can be commissioned faster. Contrary to a remedy with capillaries, it generally does not require any test run.
Reduced maintenance effort
The maintenance effort is leaner: In case of a fault, only the procedure transmitter concerned must be replaced. In contrast, with measuring differential pressure with capillaries, the complete measuring arrangement should be replaced.
Note
Further information on the model CPT-2x and IPT-2x process transmitters, which are suitable for electronic differential pressure measurement for level monitoring, is available on the WIKA website.