Preventing the ingress of moisture through the cable of submersible pressure transmitters and level probes?

If you need to measure the degree of a liquid easily and reliably, most people will do this using hydrostatic pressure measurement, e.g. with a submersible pressure transmitter or a so called level probe. The characteristic submersed application implicates a maximum contact with the surrounding, mainly water-based medium, respectively to ?moisture?.
Exposure isn’t just limited to the wetted parts of the pressure sensor housing, but also to the complete immersed length of the cable. In addition, beyond your directly immersed level probe parts, the cable, and in particular the cable end, tend to be exposed to moisture as a result of splash water, rain and condensation. That is true not merely during operation, but a lot more during installation and commissioning, or when maintenance or retrofitting is required. Irrespective of the mark application, whether in water and wastewater treatment or in tank monitoring, moisture ingress in to the cable ends of the submersible pressure transmitter may appear early and irreversibly with insufficient protection measures, and, in almost all cases, lead to premature failure of the instrument.
The ingress of moisture into the cable outlet and from there on downwards into the electronics of the level probe should be actively eliminated by preventive actions by the user. To measure the level with highest accuracy, the varying ambient pressure above the liquid media, that is also ?resting? on the liquid, must be compensated against the hydrostatic pressure acting on the pressure sensor (see article: hydrostatic level measurement).
Ventilation tube
Thus, it really is logical that there is a constant risk of a moisture-related failure because of moisture ingress (both via the ventilation tube and through the actual cable itself) if you can find no adequate precautionary measures. To compensate the ambient pressure ?resting? on the media, a ventilation tube runs from the sensor element within the level probe, through the cable and out from the level probe by the end of the cable. Because of capillary action within the ventialation tube useful for ambient pressure compensation, moisture may also be transported from the encompassing ambience right down to the sensor.
Thus not merely air, but additionally moisture penetrates into the tube, hence the sensor inside the probe and the electronics around it is usually irreparably damaged. This may lead to measurement errors and, in the worst case, even to failure of the level probe. To prevent any premature failure, the ingress of moisture in to the ventilation tube should be completely prevented. Additional protection against moisture penetration through the ventilation tube is supplied by fitting an air-permeable, but water-impermeable filter element by the end of the vent tube.
bare wires
Never to be ignored is also the transport of the liquid through high-humidity loads across the only limitedly protected internals of the cable, e.g. across the wires, all the way right down to the submersible pressure transmitter. As Unparalleled leading manufacturer, WIKA uses appropriate structural design to prevent fluid transport, as far as possible, into the electronics of the submersible pressure transmitter. Because of molecular diffusion and capillary effects, a guaranteed one-hundred percent protection over the full lifetime of the submersible pressure transmitter, however, is never achievable.
It is therefore recommended that the cable is definitely terminated in a waterproof junction box with the appropriate IP protection (e.g. IP65) which is matched to the installation location. If this cable junction box is subjected to weather and varying temperature conditions, it is also recommended to pay attention to a controlled pressure equalisation to be able to avoid the formation of condensation or perspiration water and pumping effects. To address this technical requirement, as an accessory to a submersible pressure transmitter, it is possible to order a link box having an integrated air-permeable, water-impermeable membrane.
Ultimately, moisture ingress can happen not only through the exposed end of the cable, but additionally through mechanical damage to the cable sheath or because of liquid diffusion because of improper chemical resistance of the cable material. In the article ?Selection criteria for the prevention of moisture-related failures of submersible pressure transmitters or level probes? this failure mode is described at length.
WIKA offers comprehensive solutions for your hydrostatic-pressure level measurement. For further assistance in selecting the submersible pressure transmitter most suitable for your application, please use our contact form.
Please find more info with this topic on our information platform ?Hydrostatic level measurement?